Troubleshooting Guide Troubleshooting System Interfaces
Dynamic Range and Noise Basics
The human ear itself has a dynamic range, from the
threshold of hearing to the threshold of pain, of about 140 dB. Up to 120 dB of
dynamic range may be required in high-end “audiophile” sound systems
installed in typical homes [Ref 1].
In video systems, 50 dB is generally accepted as a threshold beyond which no
further improvement in images is perceivable, even by expert viewers.
The dynamic range
of an electronic system is the ratio (generally expressed in dB) of its maximum
undistorted signal output to its residual noise output or noise floor. The signal-to-noise
ratio or SNR is the ratio of a reference level signal output to noise
floor. The headroom or overload margin
of a device is the ratio of its maximum undistorted signal output to a
reference level signal. Therefore, dynamic range = SNR + headroom if all are
expressed in dB.
The usable dynamic range of a system is most often
compromised by its noise floor. Noises such as hum or buzz are generally much
more irritating to a listener than truly random noise, which is heard as hiss.
Once a signal is contaminated by noise, it's essentially impossible to remove
it without degrading the original signal. The dynamic range of an entire system can be
no better than its weakest link.
Noise must be minimized all along the signal path. In general, each downstream
(between source and listener/viewer) device must have a dynamic range 10 to 15
dB better than the source in order to preserve the original dynamic range. Of
course, this assumes that the system gain structure is such that the dynamic
range of each device is fully utilized.
The SIGNAL INTERFACES, rather than the
equipment itself, are most likely to degrade dynamic range in the vast majority
of systems.
Unbalanced Interface Basics
An unbalanced interface uses a pair of wires to carry the
signal from one device to another. One wire is grounded and the other carries the
signal.
Every output has an impedance (measured in ohms) called
its “output impedance”. For practical reasons, real outputs can't
have zero-ohm output impedance. Likewise, every input has an impedance
(measured in ohms) called its “input impedance”. For practical
reasons, real inputs can't have infinitely-high input impedance.
When an output is connected to an input, a series circuit
called a “voltage divider” is formed, where voltage drops are
proportional to impedance (see Figure 1). The input impedance of Device B is
called a load on the output of Device A.

Since the purpose of an interface is to transfer maximum
signal voltage from output to input, it’s desirable for Zi
to be much higher than Zo. For typical equipment, Zo ranges from 100 Ω to 1 kΩ and Zi
ranges from 10 kΩ to 100 kΩ, transferring 90% to 99.9% of the available signal
voltage.
Manufacturers and users alike often confuse “output
impedance” with “load impedance”. Actual output impedance is
often missing from spec sheets and, instead, something like “20 kΩ minimum
load impedance” is the only description of an output.
Actual output impedance can be very important to know.
For example, when an output drives a long cable, high output impedance can
seriously degrade treble response. The capacitance of shielded audio cable,
typically about 50 pF per foot, and the actual output
impedance form a low-pass filter. If the output impedance is 1 kΩ (not uncommon
in consumer equipment), response at 20 kHz will be - 0.5 dB for 50 feet, – 1.5
dB for 100 feet, and – 4 dB for 200 feet of cable. If the output impedance were
lower, say 100 Ω, the effects would be insignificant.
There is a common misconception about “impedance matching” of audio
outputs and inputs. This use of a load impedance equal
to the source impedance results in maximum power
transfer, but the object of an audio interface is to transfer voltage, not
power. Matching throws away half the signal voltage and places an unnecessary heavy load on the output.
Because video and RF signals have much shorter
wavelengths than audio, they are true “transmission lines” which must
be properly “terminated” with the proper or
“characteristic” impedance of the cable at each physical end. Unterminated
or misterminated cables can cause
reflection of high frequency energy from one end of the cable to the other,
causing visible “ghosts” or “rings” in video images.
Virtually all video outputs and most video inputs have 75 Ω impedances which
properly terminate 75 Ω cables. Some video inputs have a switch marked
“hi-z” which raises their impedance to several thousand ohms,
allowing them to “bridge” or ‘loop-thru’ a line without terminating
it. This can be used, for example, to monitor video sent from a camera to a
recorder. — the camera terminates one end of the cable, the recorder
terminates the other end, and the monitor bridges the cable between them.
Power Line and Grounding Effects in Real-World Systems
Significant “noise” voltage will always exist
between the chassis grounds of any two devices in AC powered systems, whether
safety grounded or not. This must be accepted as a fact of life. This voltage
is the dominant noise source in most systems, NOT noise “picked up by
cables” as is so widely believed. Power line noise currents are coupled
through equipment power transformers and flow in system ground and interface
wiring, creating “ground noise” voltages.
Many appliances and consumer electronics are supplied
with two-prong AC plugs. Sometimes called double insulated,’ these devices are
specially designed to meet strict UL and other requirements to remain safe even
if one of their two insulation systems fails. Often there is a
“one-shot” thermal cutoff switch inside the power transformer or
motor windings to prevent overheating and subsequent insulation breakdown. ONLY
equipment originally supplied with two-prong plugs is safe to operate without
safety grounding. Equipment originally supplied with three-prong, grounding
plugs MUST NEVER have the safety grounding defeated.
* DON’T CREATE A LETHAL SHOCK HAZARD *
Never, never use
devices such as three prong to two prong AC plug
adapters, sometimes called “ground lifters” to solve
a noise problem. A “ground adapter” is actually designed to
provide a safety ground (via the cover plate screw to a grounded outlet) in
cases where a three prong plug is used with a two conductor outlet. Remember that the audio, video, or other
cables which connect equipment together can also carry lethal voltages throughout the system if just one “ground lifted” device fails. There's simply no
excuse for “ground lifting” ––– the resulting legal liability can
bankrupt a business.
As shown in Figure 2, power line noise current flowing in
the shield of unbalanced signal interconnects causes a voltage drop which
directly adds to the signal. This causes hum and buzz
in audio signals and hum bars or “sparkle bands” in video signals. In
ungrounded equipment, the coupling is capacitive which tends to make the noise
a harmonic-rich buzz’ rather than more fundamental hum’ which is more
common when equipment is grounded. Power line harmonics and high frequency
noise is created by power supplies in electronic equipment, fluorescent or
dimmer controlled lights, and intermittent or sparking loads such as switches,
relays, or brush type motors.

As shown in Figure 2, inter-chassis noise current flows
in the wire connecting points A and B, causing a small voltage drop to appear
across it. The signal actually delivered to device B is the sum of all the
voltages in the loop from point A to C, which now includes the noise. Because
the wire impedance is “common” to both signal and noise current
paths, this coupling mechanism is called common impedance
coupling.
At power line (hum) frequencies, the impedance of a wire
(or cable shield) is effectively equal to its DC resistance. According to Ohm’s
Law, E = I x R. Therefore, the low frequency noise voltage E depends on
inter-chassis current I and the resistance of the cable
shield R. Consider a 25 foot interconnect cable with foil shield and a
#26 AWG drain wire. From standard wire tables (or actual measurement) its shield
resistance is found to be 1.0 Ω. If the interchassis
current is 300 µA, the noise voltage will be 300 µV. Since the normal consumer
reference signal level is –10 dBV or 300 mV, the
noise will be only 20 x log (300 µV / 300 mV) = –60 dB relative to the
reference signal. For most systems, this is a very poor signal to noise ratio.
Common–impedance coupling can become very severe between
two “grounded” devices, since the ground noise in the building wiring
is effectively forced across the unbalanced cable's shield by the parallel
connection.
Troubleshooting System Interfaces
Finding out how and where such noises enter the system
can be a frustrating, time–consuming experience. But a significant part of
troubleshooting involves the way you think about the problem. For example, don’t
fall into the trap of thinking, just because you’ve done something a particular
way many times before, that it can’t be the problem. Even things that can’t go wrong, do.
However, the source of many problems either reveals
itself or can be simply deduced if we just gather enough information. It’s
important to have as many clues as possible before you try to solve a problem.
And write everything down . imperfect
recall can waste a lot of time.
Ask lots of questions. Troubleshooting guru Bob Pease
suggests these basic questions [Ref 2]:
1. Did it ever work right?
2. What are the symptoms that tell you it’s not working
right?
3. When did it start working badly or stop working?
4. What other symptoms showed up just before, just after,
or at the same time as the failure?
Sketch a block
diagram of the system. The following is an example:

1. Show all interconnecting cables, indicating
approximate length. Note any balanced inputs or outputs. Generally, stereo pairs can be
indicated with a single line.
2. Note any equipment which is grounded via its 3–prong
power plug.
3. Note any other ground connections such as cable TV or
DSS dishes.
Use the equipment’s
own controls, with some logic, to provide additional clues:
1. If the noise is unaffected by the setting of a volume
control or selector, it must be entering the signal path after that control.
2. If the noise can be eliminated by turning the volume
down or selecting another input, it must be entering the signal path before
that control.
Testing to Find Problem Interfaces
Some tests which involve disconnecting cables can now
further pinpoint the problem. These tests involve the
use of test adapters’ which effectively allow the system to test itself for
most noise problems. The tests can specifically differentiate these problems:
1.
Common–impedance coupling in the cable,
2.
Magnetic or electrostatic pickup by the cables, or
3.
Internal common–impedance coupling in badly designed equipment.
The test adapters may be purchased from Jensen as ISO–MAX
part numbers TAR1 for the audio RCA version or
TA–R75 for the video RCA version. You may also
build them and/or adapt them for
use with other connector types as shown in Figure 4. Since these devices do
NOT pass signal, they should be clearly marked
so that they don’t accidentally find their way into a system.
Each signal interface is tested using a four–step
procedure. If a specific interface or portion of the system has not been
identified, start at the inputs to the power amplifiers (for audio systems) or
the input to the monitor (for video systems) and work backwards toward the
signal sources.
Be very careful when performing the tests not to damage
speakers or ears! The surest way to avoid possible damage is to turn off the
power amplifier(s) before disconnecting or re–connecting cables for each test
step.
Test stereo signal paths using two adapters, using them
simultaneously for L and R, as described in the procedure.
Step 1 – Unplug the cable from the input of
Box B and plug in only the adapter as shown below.

*Is the system output quiet?
No — the
problem is either in Box B or further downstream
Yes — go to
next step
Step 2 – Leaving
the adapter in place at the input of Box B, plug the cable into the adapter as
shown below.

*Is the system output quiet?
No — the
problem is either in Box B or further downstream. If Box B is a power amplifier
driving normal (ungrounded) speakers, this test result means there may be an
internal common–impedance coupling problem in Box B. The hummer’ test can be
performed to confirm this. See Jensen application schematic AS032 for more
details. Have the unit repaired, modified, or replace
it with one which is properly designed.
Yes — go to
next step
Step 3 – Remove
the adapter and plug the cable directly into the input of Box B. Unplug the
other end of the cable from the output of Box A and plug it into the adapter as
shown below. Do not plug the adapter into Box A or let it touch anything
conductive.

*Is the system output quiet?
No — the noise
is coupling into to the cable by induction. This is most often caused by a
strong magnetic field near the cable. Such magnetic fields are produced by
power wiring, power transformers, and TV or computer CRT displays.
Electrostatic coupling is also possible, but rare in a cable which has a
grounded outer shield. Route all signal cables to avoid such strong fields.
Yes — go to
next step
Step 4 – Leaving
the adapter in place on the cable, plug the adapter into the output of Box A as
shown below.

*Is the system output quiet?
No — noisy
ground currents are being coupled by the common–impedance of the cable shield.
Install an ISO–MAXR ground isolator at the input of Box B.
Yes — the
noise is coming from (or through) the output of Box A. Perform these same tests
on the cable(s) connecting Box A to upstream devices.
Systems with Multiple Grounds
If a system contains two or more pieces of grounded
equipment, a ground loop may be formed as shown in Figure 5.

Because there is often substantial ground noise voltage
between the CATV cable shield and the safety ground for the sub–woofer, a
relatively large noise current may flow in the shield of any signal cables
which are part of the ground loop. In unbalanced interfaces, this current flow
results in common–impedance coupling which directly adds noise to the signal.
In general, the amount of noise added is in direct proportion to the cable’s
length. This example system would exhibit a loud hum regardless of the input
selected or the setting of the volume control because of ground noise current
flow in the 20 foot cable.
It might be slightly louder if the TV input were selected
and the volume turned up because the ground noise current also flows in the 3
foot cable.
You might be tempted to break’ this ground loop with a
ground lifter at the sub–woofer. DON’T !!
A safe solution is to break the ground loop by installing
a ground isolator in the audio signal path from preamp to sub–woofer as shown
in Figure 6. A high performance ground isolator, like the Jensen ISO–MAXR
CI–2RR, should always be installed at the receiving end of the cable as shown.

Another safe solution is to break the ground loop by
installing a ground isolator, such as the Jensen ISO–MAXR VR–1FF, in the CATV
signal path at the TV as shown in Figure 7.

When to Add a Ground Connection
Since most unbalanced interfaces are made to consumer
equipment which has no safety ground, isolating the interfaces may leave the
chassis “floating” with no ground reference at all. This can allow
the voltage between input and output of the isolator to approach 120 volts AC.
This is not dangerous but it puts an extreme (and unnecessary) rejection burden
on the isolator.
The problem is easily solved by adding separate grounding
connections to the “floating” gear as shown in Figure 8. This is most
easily done by replacing the 2 prong plug with a 3 prong type and adding a
(green or green/yellow preferred) wire connected between the safety ground pin
of the new AC plug and a chassis ground. If there is any doubt whether a screw,
which may be convenient for the chassis connection, is actually grounded, use
an ohmmeter to check for continuity between the screw and the outer contact of
an RCA connector (which itself can be used if no other point is available).

More Tips to Reduce Noise
Keep cables as short as possible! Longer cables increase
the coupling impedance. Serious noise coupling is nearly certain with 50 or 100
foot cables. Even much shorter cables can produce severe problems if there are
multiple grounds. Never coil excess cable length.
Use cables with heavy gauge shields! Cables with shields
of foil and light gauge “drain wires” increase coupling impedance.
Use cables with heavy braided copper shields, especially for long cables. The
only property of cable which has any significant effect on audio–frequency
noise coupling is shield resistance, which can be measured and compared with an
ordinary ohmmeter.
Maintain good connections! Connectors left undisturbed
for long periods can develop high contact resistance. Hum, buzz, or other
interference which changes when the connector is wiggled indicates a poor
contact. Use a good commercial “contact fluid” and/or gold plated
connectors to help prevent such problems.
Don’t add unnecessary grounds! Additional grounding of
equipment will generally increase circulating noise currents rather than reduce
them. As emphasized earlier, NEVER disconnect or “lift” a safety
ground or lightning protection ground to solve a problem !
the practice is both illegal and very dangerous.
Use ISO–MAX ground isolators at problem interfaces! These
transformer based isolators magnetically couple the signal while completely
breaking input to output connections. This stops the noise current flow in the
cable’s shield, eliminating common–impedance coupling. A variety of isolators
are available for audio, video, and CATV signals.
Special ground isolators are required for digital
satellite TV receivers. A lightning safety ground is required for the dish’
antenna. Because DC power for dish electronics is carried by the cable
connecting it to the receiver, conventional CATV type ground isolators can't be
used because they block DC power. One alternative is to break the ground loop
with a special bidirectional coupler which works through
window glass. It inductively couples power in one direction and capacitively couples the signal in the other direction.
Another is to break the ground loop by inserting a special gas discharge tube
based isolator device between the coax grounding block and the earth ground
rod. This device effectively opens the ground path, connecting it automatically
only when required to discharge high voltages.
Troubleshooting even large, complex systems becomes
manageable if testing always uses the technique of working backwards toward the
signal sources. Some simple measurements (or estimates) on system equipment and
cables make it possible to actually predict hum levels and
identify the problem interfaces before a system is installed [Ref 3].
About Contractor’s A/V.com
Contractor’s A/V.com is a resource for everyone (the public), from those new to technology through the most sophisticated professionals. CAV offers a one-stop resource to understand products and how to use them with a bias only for quality and value. Contractor’s A/V.com was created for this purpose since no other effective resource quite like it exists. Our objective is to help our customers make an informed purchase decision so as to get the most from their technology products and purchases.
Still Have Questions?
Feel free to e-mail us at techhelp@contractorsav.com or call us at (888) 848-4228.
Contractor’s A/V.com – Technology Made Simple™ |
References
[1] Louis Fielder, Dynamic Range
Issues in the Modern Digital Audio Environment, Journal of the AES, May, 1995.
[2] Robert A. Pease, Troubleshooting Analog Circuits,
Butterworth–Heinemann, 1991.
[3] Jensen Transformers, Application Note AN004.
 |